Cast iron durability and Burnham quality craftsmanship make the Series 2 residential gas boiler ideal for the replacement and new construction markets. Available in 14 models, including the high efficiency Series 2H, the Series 2 line combines traditional atmospheric draft design with proven boiler controls to ensure reliable, trouble-free operation. These boilers feature Step Opening Gas. Burnham boilers are very efficient and a smooth boilers that are present in our market today. But, do you know where they come from? They are manufactured by Burnham Commercial. It is a leading boiler company, manufacturing and marketing high quality boiler system for both commercial and industrial applications. Quick Annual Check up on old Burnham Gas BoilerLAVIMONIERE PRODUCTIONS,LLC subscribe to my channel https://www.youtube.com/channel/UC4mZGMmJ1kOaOG1oRACZDbQ. Burnham boilers are a great option if you are installing a boiler system in your home. However, just like any other product, Burnham boilers have problems that may arise from time to time. Because Burnham boilers are available for many different types of fuels, it is important to understand what problems may arise for your.

Burnham ALP105 boilers troubleshooting

CODECONDITIONPOSSIBLE CAUSES
b 08Pressure switch circuit open• Blockage in intake or vent system.
• Vent and/or intake system not constructed in accordance with Part VI
• Blocked or leaking pressure switch tubing
• Heat exchanger or burner blockage
• Terminals exposed to high winds
• Blockage in condensate trap above vent.
b 18MCBA supply sensor detected temperatures in excess of200°F• Heating load at time of error was far below the minimum firing rate c boiler
• Defective primary pump or no flow in primary loop (Piping Method
• Control system miswired so that boiler operation is permitted when n are calling
b 19MCBA return sensor detected temperatures in excess of200°F• See possible causes for “bl8”
• Flow through boiler reversed
• Sensor wiring reversed
b 24MCBA is reading a return sensor temperature higher than the supply sensor temperature. Condition must be present for at least 75s for this error code to appear.• Flow through boiler reversed. Verify correct piping and pump orienta
• No boiler water flow. Verify that system is purged of air and that appi valves are open.
• Sensor wiring reversed.
• Supply or return sensor defective.
b25Supply water temperature has risen too quickly• See possible causes for “bl8”
• Inadequate boiler water flow. Verify' that pump is operating and that pump and piping are sized per Part VIII of this manual
b26Boiler safety limit, or external limit wired across terminals 3&4, is open.• See possible causes for “bl8”
• Defective supply sensor.
b 30Temperature rise between supply and return is too high.• Inadequate boiler water flow. Verify' that pump is operating and that pump and piping are sized per Part VIII of this manual
b 61Pressure switch circuit closed with fan off• Blockage in pressure switch hose
• Pressure switch wires shorted together
• Defective pressure switch
• Loose or miswired fan speed harness (if “b61” error code is observed while fan is running)
b65Fan is not achieving set point speed• Loose or incorrect fan speed control connection
• Defective fan
E 00A flame signal was present when there should be no flame.• Defective gas valve make sure inlet pressure is below maximum on rating plate before replacing valve.
E 02Flame failure after 5 tries to restart• No gas pressure
• Gas pressure under minimum value shown on rating plate
• Gas line not completely purged of air
• Defective Electrode
• Loose burner ground connection
• Defective Ignition Cable
• Defective gas valve (check for 24 VDC at harness during trial for ignition before replacing valve)
• Air-fuel mixture out of adjustment consult factory
E 03Gas valve error• Loose or defective gas valve harness. Check electrical connections.
• Defective gas valve (check for 24 VDC at harness during trial for ignition before replacing valve)
E 04Power failure occurred after lockout• Some other error on this list occurred and power to the boiler was then interrupted. Reset control and see if hard lockout reoccurs.
E 05, E 06, E 07, E 11Internal control failure• Reset the control. If problem reoccurs, replace the MCBA.
E 12Low water cut-off circuit open• If yellow light on LWCO is on, system is low on water
• If neither yellow nor green light is on, check LWCO harness and check for 24VAC across AT140 transformer
E 13, E 14, E 15, E 16, E 17Internal control failure• Reset the control. If problem reoccurs, replace the MCBA.
E 18MCBA supply sensor detected temperatures in excess of 200°F for an extended period of time• See possible causes for “b18' error. Also, check safety limit for proper operation.
E 19MCBA return sensor detected temperatures in excess of 200°F for an extended period of time• See possible causes for “b19“ error.
E 28Blower is not running when it should or fan speed signal not being detected by MCBA• Loose connection in 120 VAC fan wiring
• Loose or miswired fan speed harness
• Defective fan
E 29Blower fan speed has not returned to zero rpm• Miswired fan speed harness
• Defective fan
E 31Shorted supply temperature sensor• Shorted or miswired supply sensor wiring
• Defective supply sensor
E 32Shorted return temperature sensor• Shorted or miswired return sensor wiring
• Defective return sensor
E 35Flue gas temperature sensor short circuit• Shorted or miswired flue temp sensor wiring
• Defective flue temp sensor
E 36Supply water temperature sensor circuit open• Loose or miswired supply sensor wiring
• Defective supply sensor
E 37Return water temperature sensor circuit open• Loose or miswired return sensor wiring
• Defective return sensor
E 40Flue gas temperature sensor circuit open• Loose or miswired flue temp sensor wiring
• Defective flue temp sensor
E 44Internal control failure• Reset the control. If problem reoccurs, replace the MCBA.
E 52Flue gas temperature over 230°F• Heat exchanger needs to be cleaned
• Boiler over-fired
• Air-fuel mixture out of adjustment consult factory
E 60Internal control failure• Reset the control. If problem reoccurs, replace the MCBA.

Burnham ALPINE boilers troubleshooting

ConditionPossible Cause
Display Blank, Fan off, LWCO lights off, no green power light on Sage2.1 ControllerNo 120VAC Power at boiler. Check breaker and wiring between breaker panel and boiler.
Display Panel Blank, Fan runningLoose 120VAC connection wiring between boiler J-Box and transformer Loose 24 Vac connection wiring between transformer and Sage2.1 Loose 5 Vdc connection wiring between display and Sage2.1
Boiler fires, but display panel is blankLoose 5 Vdc connection wiring between display and Sage2.1 Defective display
Boiler not responding to call for heat, Status screen reads “Central Heat T-Stat Off’Boiler is not seeing call for heat. Check thermostat or zone wiring for loose connection, miswiring, or defective thermostat/zone control.
Boiler not responding to a call for heat, “Standby” status is showing.Boiler is not firing. There is no call for heat or there is a call for heat and the temperature is greater than setpoint.
Boiler not responding to Domestic Hot Water Heat RequestBoiler is not sensing Domestic Hot Water Heat Request. Check wiring for loose connection, miswiring, or defective indirect water heater aquastat.
Boiler Running but System or Boiler Circulator is not runningCheck wiring for loose connection, miswiring. When there is a Domestic Hot Water Heat Request the System or Boiler pumps will be forced “off’ when there “Run Pump for” parameter is set to “Central heat, off DHW demand” or “Central Heat, Optional Priority”. This has been set to allow all of the heat to be provided for fast indirect water heater recovery. After one hour of “priority protection” or the end of the Domestic Hot Water Heat Request the system and boiler pumps will be free to run.
Home is cold during mild weather daysIncrease Low Boiler Water Temperature parameter 5°F per day.
Home is cold during cold weather daysIncrease High Boiler Water Temperature parameter 5°F per day

Burnham boilers are very efficient and a smooth boilers that are present in our market today. But, do you know where they come from? They are manufactured by Burnham Commercial. It is a leading boiler company, manufacturing and marketing high quality boiler system for both commercial and industrial applications.

It’s their efficiency that gave them the edge over other companies. They have efficiency percentage of up to 96%. That’s leaves only 4% of wasted energy. Burnham Commercial is still working on to improve their efficiency level every day. They are designed and manufactured to the highest quality standards with American made materials. Burnham commercial is located in Lancaster, having state-of-the-art manufacturing machines to meet their quality demands.

Why use burnham boilers?

Burnham boilers are the best residential hydronic boilers around in the market today.

Winters can be really disastrous. During winter, we face many problems. Cold is the major problem one has to face during winter.

Burnham gas boiler manual

For example, when you bath, the water might suddenly turn cold. Furthermore, you might be forced to pay huge electricity bills with your old boiler.

Burnham boilers will help you maintain a cozy warm environment in your house. It also works very fast to meet the heat demands after turning on the device.

How Efficient are burnham boilers?

Burnham Boilers Manualsnewnevada

Burnham boilers are extremely efficient. What this means is that it makes use of electricity efficiently. This greatly helped to lower my electricity bill. It’s impossible to reduce the cost per unit of electricity. That’s why we have to make use of the electricity efficiently.

Let me explain. All electrical appliances have a certain percentage of efficiency level. The efficiency percentage indicates how well it can convert the electrical energy into useful energy. The remaining percentage indicates the wasted energy such as sound and heat energy.

Heat is a by-product of almost all electrical appliances. When electrical appliances such as music players and cell phones produce heat energy, it is considered as a wasted energy. This is because heat energy produced in music player and cell phones are not being used for any purpose.

U S Boiler Company Burnham

Thus, one of the most wasted energy in electrical appliances is heat energy. But, this is not the same case for heaters used for home heating.

In fact, Heat energy is an energy utilized by them to provide warmth in our house. Thus, home boilers usually have a high percentage of electrical efficiency. But to achieve that high efficiency, the boiler should be made in a way that maximizes the electrical input. Burnham boilers are made in a way that fully maximizes the electrical input. They are made in America with high quality materials that increase the percentage of efficiency.

Energy efficient appliances such as Burnham boilers are not only good for reducing your utility bill but they would also release the demand for electricity by the equivalent of 25 large power plants according to the American Council. All that we need to do is to increases the energy-efficiency in our major appliances by 10 to 30%. Burnham boilers can help you achieve just that.

Burnham Boilers Website

Are burnham boilers hard to maintain?

Old and inefficient boilers require great deal of time and money maintaining it. In the long run the maintenance fee might exceed the cost price that the old boiler was bought for. If that’s your case you need to lookout for another Hydronic boiler like burnham boilers. They do not need a great fortune running and maintaining it. In fact, I had not faced any serious issues with my burnham boilers yet.

Negative factors about burnham boilers

Burnham Boiler Model Numbers

Not everything in this world in perfect. Burnham boilers are not any exception. They too have their share of downfalls.

Firstly, burnham boilers come with a hefty price tag. Its expensive price tag might make you initially to consider other choices. But you will be very glad if you chose burnham boilers. Even though you might have a slight hesitation to buy the burnham boilers at first for its price, it will be compensated by the fact that it requires little to no maintenance. Once it’s properly set up, it will work for a long time.

Talking about setting up the boiler, I have to admit that the process might be tedious and complicated for you. But with the good customer support from burnham boilers company, you will be able to set up the boiler the right way. I have seen some people who complain that they did not get any real value from burnham boilers. They complained that burnham boilers did not work properly, have leakages and etc…

Burnham Residential Boilers

All this will only happen if you have failed to set up the device properly. So, please do not take this lightly. Take careful steps in setting up your burnham boilers.

Summary of all positive and negative points about burnham boilers

Positive points about burnham boilers:

– Very efficient (Reduces your electrical bills)

– Little to no maintenance needed (save money and frustration)

– Works very fast (Less waiting time for radiation to take place)

– High quality boiler (Made from American made materials, it has excellent construction, sound design, and ace performance)

Negative Points about Burnham Boilers:

-High cost (Can be compensated by its long life span and performance)

Burnham Boilers Manuals

-Complicated setting up process (Call for help from Burnham Commercial)

Burnham Spirit Boiler Manual

I hope that I had given you the required information about burnham boilers. That’s not all; you still have some reading up. Please read my other blog posts on burnham boilers. I will always stick with my motto, which is to help people make better informed decisions regarding burnham boilers.

Related posts:

–>Three types of burnham boilers efficiency and their definition

Burnham

–>Choosing Burnham Boilers that suits your needs

–>Hydronic Heating and Burnham Boilers

–>How much can you save using Burnham Boilers?